ProVent Systems Inc.
1355 Capital Circle
Lawrenceville, GA, 30043

Tel: 800-262-5355
Fax: 770-339-1784

Rules for the ProVent® Stack and StackVent Fitting

The stack must be sized by the total number of fixture units (D.F.U.) discharging into it.  Chart 1 provides the number of fixture units by individual fixture. The sum of the fixture units for all fixtures discharging into the stack equals the total fixture units.  Chart 3 provides the required stack size by total fixture units.  The stack size shall continue full size through the roof.

 

A ProVent Stack Fitting is required to be used at each floor level when the horizontal soil or waste branch collected is either the same size or one pipe size smaller than the vertical ProVent Stack Fitting.

 

If there are no branch connections at a floor level, there is no need to use the ProVent Stack Fitting. Instead, a double in-line offset must be used in its place.  The vertical interval between the Stack Fitting and the in-line offset shall not exceed 20 feet and no more than two (2) consecutive double in-line offsets can be used.

 

Waste branches that are two (2) pipe sizes smaller than the stack can be connected with a sanitary tee or wye directly into the ProVent stack.

 

Offsets in the stack of more than 60 degrees require a ProVent Base Fitting with a pressure relief vent line tied in to the top vertical portion of the stack.  Branch piping can be connected to the offset soil piping.  A 45 degree stack offset is not considered an offset.  Waste branches (1) one pipe size smaller can be connected to the pressure relief vent line with the exception of washing machine wastes.  It is recommended that Washing machine wastes should be isolated from other fixtures.  If they must be combined, call for technical support.

 

The building drain size is determined by the total fixture unit load (Chart 4) from the combination of stacks and other soil or waste branches that discharge into it (Chart 1, Chart 2 and Chart 3).

 

Stacks may offset above the highest fixture served. When the horizontal offset exceeds twenty (20) feet, the diameter of the horizontal offset and the vent through the roof must be increased one pipe size

 

Combinations of vent stacks may be tied together above the highest fixture served before going through the roof.  The combined vertical stack must be increased (1) one pipe size larger than the combined stacks.  If the distance between the two (2) stacks that connect is greater than twenty (20) feet, the horizontal branch must be one (1) pipe size larger than the downstream stack.

Copyright © 2006 by ProVent Systems Inc.  All rights reserved.